Huawei FusionModule2000 V500R002C03 Maintenance Manual page 23

Smart modular data center
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Cente
Maintenance Guide
Item
input power cables
and output power
cables on the PDC or
the new main way.
Check whether there
is any sign of rodent
movements inside the
PDC or new main
way.
Check whether the air
intake and exhaust
vents of devices are
blocked.
Table 4-3 Monthly maintenance for the cooling system
Item
Operation
Condensate pan
Visual
and liquid level
observation
detector
Air filter
Visual
observation
Visual
observation
Compressor
Visual
observation
Visual
observation
Listen to the
compressor
operating sound.
Pipe
Visual
observation
Visual
observation
Visual
Indoor fan
observation
Visual
observation
Issue 03 (2019-12-04)
Operation
Visual observation
Visual observation
Standard
Check that the condensate water
pan and liquid level detector have
no scale.
Check that the filter is not blocked.
Check that the filter is not damaged
or distorted.
Check that the compressor is
secured properly.
Check that there is no oil stain on
the compressor service valve.
Check that the sound of the
compressor is properly.
The refrigerant pipe does not leak
or corrode, and is properly wrapped
with thermal insulation foam.
Check that the refrigerant pipe
support is intact and securely
installed.
Check that the indoor fan guard is
not distorted.
Check that the indoor fan blades are
intact.
Copyright © Huawei Technologies Co., Ltd.
Standard
The terminals are intact
and secure and free from
spark signs and rust.
There is no sign of rodent
movements in the PDC or new
main way.
The air intake and exhaust
vents of devices are not
blocked.
4 Routine Maintenance
Troubleshooting
Secure output terminals.
If there is a sign of rodent
movements, ask a
professional to trap the
animals.
Remove any blockages
from the air intake and
exhaust vents of devices.
Troubleshooting
Clean up the scale from the
condensate pan and liquid level
detector.
Remove the air filter and clean
it. (water cleaning is
recommended).
Replace the air filter.
Tighten the compressor screws.
Clean the refrigerant oil.
Replace the compressor.
Check for and repair leaks, and
wrap the thermal insulation
foam again.
Replace the pipe support and
secure it.
Maintain or replace the fan
guard.
Replace the fan.
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusionmodule2000

Table of Contents