4.5 Semiannual Maintenance

Table 4-8 Semiannual maintenance for the power supply and distribution system
Item
Operation
Visual
UPS cleanliness
observation
Oxidation of
Visual
metal
observation
components in
the PDC or smart
busway
Table 4-9 Semiannual maintenance for the cooling system
Item
Operation
Sensor
Use a high-precision
humidity and temperature
sensor to calibrate the
humidity and temperature
sensors inside and outside
the cabinet.
Evaporator
Visual observation
Welding spot and
Check that the welding spots
needle valve
and needle valves do not leak
using soapy water, or check
that they are free from oil
stains.
Smart cooling
Visual observation
product
cleanness
Table 4-10 Semiannual maintenance for the management system
Item
Operation
Check the
On the ECC800
availability of the
WebUI, choose
smart ETH
Monitoring >
gateway.
System > Smart ETH
Gateway Group >
Smart ETH Gateway
Issue 03 (2019-12-04)
Standard
The white paper that you use
to wipe the panels is clean.
No metal component rusts.
Standard
The temperature
deviation is lower than
1° C or humidity
deviation is lower than
5%.
The evaporator fins are
not pushed down.
Check that the welding
spots and needle valves
do not leak using soapy
water
The white paper that you
use to wipe the panels is
clean.
Standard
On the ECC800 WebUI,
check that the PoE port
connection and power
supply in the smart ETH
gateway is normal.
Copyright © Huawei Technologies Co., Ltd.
4 Routine Maintenance
Troubleshooting
If the white paper becomes dirty, clean
up the dust, especially from the air filter
on the front door, or replace the air filter.
If any metal component suffers from
severe oxidation, remove the rust or
replace the component in a timely
manner.
If the component is painted, repaint it
after removing the rust.
Troubleshooting
If the temperature deviation is
greater than 1° C or humidity
deviation is greater than 5%,
the T/H sensor must be
calibrated or replaced.
Use a fin brush to organize the
fins that are pushed down.
If leaking points are found,
retrieve the refrigerant and
weld the leaking points again.
For details, contact Huawei
technical support.
If the white paper becomes
dirty, remove the dust on the
smart cooling product cabinet.
Troubleshooting
If the PoE port connection and
power supply in the smart ETH
gateway is not normal, check
whether the communications cable
is loose or disconnected. If so,
reconnect the cable. If not, replace
23