Maintenance Guide
Item
Operation
NOTE
If you open the skylight
remotely for
maintenance, manually
close the skylight after
the maintenance is
complete.
Check the
On the ECC800
availability of the
WebUI, choose
access actuator.
Monitoring > Aisle >
Access Actuator
Group > Access
Actuator to enter the
Controls page, and
remotely control the
doors.
Check the
Open the door by
availability of the
pushing the exit button.
access control
system.
Open the door by
pushing the emergency
button.
NOTE
The emergency button
needs to be pressed twice.
One press will open the
door, and the other press
will reset the emergency
button.
Check the
(Optional) Open the
availability of the
door using an
access control
authorized fingerprint.
device.
(Optional) Open the
door using an
authorized access card.
Check the
Open the door.
availability of the
revolving door
access system.
Issue 03 (2019-12-04)
Standard
The smart module aisle
doors can be normally
controlled through the
access actuator.
The door opens normally
after you push the exit
button.
The door opens normally
after you push the
emergency button.
The aisle door can be
opened.
The aisle door can be
opened.
Doors can be normally
opened through the
access control device.
Copyright © Huawei Technologies Co., Ltd.
4 Routine Maintenance
Troubleshooting
If the smart module aisle doors
cannot be normally controlled,
check whether the magnetic lock
cable is loose or disconnected. If
so, reconnect the cable. If not,
replace the access actuator or
magnetic lock.
If the other devices in the access
control system are working
properly and the door cannot be
opened by pushing the exit button,
replace the exit button.
If the other devices in the access
control system are working
properly and the door cannot be
opened by pushing the emergency
button, replace the emergency
button.
If the aisle door cannot be opened,
check the cable connection. If the
cable is properly connected, replace
the access control device.
If the aisle door cannot be opened,
change the access card. If the fault
is rectified using a different access
card, record the access card
information. If the fault persists
using a different access card, check
the cable connection. If the cable is
properly connected, replace the
access control device.
If the access control device and
actuator are working properly,
check whether the cable is properly
connected to the magnetic lock. If
not, reconnect the cable. If so,
replace the magnetic lock.
25