FusionModule1000A40 ICT Solution
Maintenance Guide
Check
Item
Smart ETH
gateway
Issue 01 (2019-03-05)
Operation
Check Standard
Power input
Input voltage:
45–55 V DC
Power output
Output voltage:
45–55 V DC
PWR
Steady on: The
indicator
power supply is
normal.
Off: No power
supply is available.
RUN
Off: The power
indicator
supply is abnormal.
Blinking slowly:
The software runs
properly (the
indicator blinks at
0.5 Hz, on for 1s
and then off for 1s)
or registration with
the ECC800 is
successful.
Blinking at short
interval: The
communication is
interrupted or the
registration with the
ECC800 fails (the
indicator blinks at 4
Hz, on for 0.125s
and then off for
0.125s).
Blinking: The
indicator blinks at
super short intervals
for 0.5s (blinking at
10 Hz, on for 0.05s
and then off for
0.05s) and then
turns off for 0.5s.
The cycle lasts for
10s.
ALM
Steady on: A fault
indicator
alarm is generated.
Off: No fault alarm
is generated.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
Check the input power cables if the
input voltage is abnormal.
For details, contact Huawei technical
support.
Check the input power cables.
Check the power supply.
Refer to ECC800 Data Center
Controller V100R001C30 User
Manual to register the device, or
contact Huawei technical support.
Refer to ECC800 Data Center
Controller V100R001C30 User
Manual to handle alarms, or contact
Huawei technical support.