Huawei FusionModule1000A40 ICT Solution Maintenance Manual page 26

Hide thumbs Also See for FusionModule1000A40 ICT Solution:
Table of Contents

Advertisement

FusionModule1000A40 ICT Solution
Maintenance Guide
Check
Item
Issue 01 (2019-03-05)
Operation
Check Standard
RUN
Off: The power
indicator
supply is abnormal.
Blinking slowly:
The software runs
properly (the
indicator blinks at
0.5 Hz, on for 1s
and then off for 1s)
or registration with
the ECC800 is
successful.
Blinking at short
interval: The
communication is
interrupted or the
registration with the
ECC800 fails (the
indicator blinks at 4
Hz, on for 0.125s
and then off for
0.125s).
Blinking: The
indicator blinks at
super short intervals
for 0.5s (blinking at
10 Hz, on for 0.05s
and then off for
0.05s) and then
turns off for 0.5s.
The cycle lasts for
10s.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
Check the power supply.
Refer to ECC800 Data Center
Controller V100R001C30 User
Manual to register the device, or
contact Huawei technical support.