Item

3.6 Quarterly Maintenance

3.6.1 Monitoring System

Table 3-10 Quarterly maintenance checklist for the monitoring system
Check
Item
Access
actuator
Issue 01 (2019-03-05)
Method
Check whether
obvious rubbish
exists around the
containers.
Check whether the
ambient
temperature,
humidity, and solar
radiation outside
the containers meet
requirements.
Operation
Check Standard
Power input
Input voltage:
36–60 V DC
Copyright © Huawei Technologies Co., Ltd.
Check
Troubleshooting
Standard
No obvious
Clean the rubbish.
rubbish exists
around the
containers.
The external
For details, contact Huawei
temperature
technical support.
and solar
radiation
requirements
of the
FusionModule
1000 are as
follows:
Temperatur
e:
Normal
tempera
ture:
-20° C to
+55° C
Low
tempera
ture:
-40° C to
+45° C
Humidity:
5%–95%
RH
Solar
radiation: ≤
2
1120 W/m
Troubleshooting
Check the input power cables if the
input voltage is abnormal.