DNP 3.0 Serial Master (OPC) User's Manual

Adding DNP OPC Server object

After the Gateway object has successfully been added, you can continue building the
object tree by adding DNP OPC Server object.
To add DNP OPC Server object:
1. Select the Gateway object in the communication structure and right-click it.
2. Add DNP OPC Server object.
By using the SCL Import function, it is possible to import an entire server's or individual
device's configurations without having to insert them manually. To open the SCL Import
function, right-click the desired object, and select SCL Import.
For more information about the SCL Import function, see COM600 User's Manual.
Connectivity Packages for certain protection and control devices can also support other
ways to build this structure, depending on the configuration of an individual device, for
example device-related object types and wizards. Typically, Connectivity Packages
include SCL description files which must be installed. For further information on these
Connectivity Packages, see the Connectivity Package of a certain device in the product
documentation.

Adding DNP Channel objects

After the server object has been successfully added, you can continue building the object
tree by adding DNP Channel objects.
To add DNP Channel object:
1. Select DNP OPC Server object.
2. Right-click the DNP OPC Server object.
3. Add DNP Channel object.
4. Rename the new object. The names of the DNP Channel objects have to be unique.

Adding DNP IED objects

After adding a subnetwork you can add device objects.
To add an IED object:
1. Select a Serial channel object.
2. Add DNP IED object.
3. Rename the new object. The names of the devices within a DNP Serial channel have
to be unique.
The maximum number of devices per Serial channel is 30.