Hand/Auto Macro; Default I/O Connections - ABB ACS150 series User Manual

0.37...4kw; 0.5...5 hp
Hide thumbs Also See for ACS150 series:
Table of Contents

Advertisement

Hand/Auto macro

This macro can be used when switching between two external control devices is
needed. To enable the macro, set the value of parameter
5 (HAND/AUTO).
For the parameter default values, see section
macros
see section
Note: Parameter

Default I/O connections

1...10 kohm
Alternative connection
for AI1. If used, switch
IU selector to U
(2...10 V voltage
signal).
1)
In the Hand mode, the frequency reference
comes from the integrated potentiometer.
2)
360 degree grounding under a clamp.
on page 79. If you use other than the default connections presented below,
I/O terminals
on page 44.
2108
START INHIBIT must remain in the default setting 0 (OFF).
I/O connection
SCR
AI
GND
2)
+10V
+24V
GND
COM
DI1
DI2
DI3
DI4
DI5
Relay connection
COM
NC
NO
Default parameter values with different
3)
Signal cable shield (screen)
Frequency reference (Auto): 4...20 mA
Analog input circuit common
Reference voltage: +10 V DC, max. 10 mA
Auxiliary voltage output: +24 V DC, max. 200 mA
Auxiliary voltage output common
Digital input common
Stop (0) / Start (1) (Hand)
Forward (0) / Reverse (1) (Hand)
Hand (0) / Auto (1) control selection
Forward (0) / Reverse (1) (Auto)
Stop (0) / Start (1) (Auto)
4)
Relay output
No fault [Fault (-1)]
3)
Tightening torque: 0.22 N·m / 2 lbf·in
4)
Tightening torque: 0.5 N·m / 4.4 lbf·in
9902
APPLIC MACRO to
1)