Parameters in the Long parameter mode
Index Name/Selection
-3 = DI3(INV)
-4 = DI4(INV)
-5 = DI5(INV)
1606
LOCAL LOCK
0 = NOT SEL
1 = DI1
2 = DI2
3 = DI3
4 = DI4
5 = DI5
7 = ON
-1 = DI1(INV)
-2 = DI2(INV)
-3 = DI3(INV)
-4 = DI4(INV)
-5 = DI5(INV)
1607
PARAM SAVE
0 = DONE
1 = SAVE
1610
DISPLAY ALARMS
0 = NO
1 = YES
1611
PARAMETER VIEW
0 = DEFAULT
1 = FLASHDROP
Description
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Disables entering the local control mode or selects the source for the local
control mode lock signal. When local lock is active, entering the local control
mode is disabled (LOC/REM key of the panel).
Local control is allowed.
Local control mode lock signal through digital input DI1. Rising edge of digital
input DI1: Local control disabled. Falling edge of digital input DI1: Local
control allowed.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Local control is disabled.
Local lock through inverted digital input DI1. Rising edge of inverted digital
input DI1: Local control allowed. Falling edge of inverted digital input DI1:
Local control disabled.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Saves the valid parameter values into the permanent memory.
Saving completed
Saving in progress
Activates/deactivates alarms
OVERVOLTAGE
(code: A2002),
DEVICE OVERTEMP
(code: A2006). For more information, see chapter
Fault tracing
on page 127.
Alarms are inactive.
Alarms are active.
Selects the parameter view, that is which parameters are shown on the
control panel.
Note: This parameter is visible only when it is activated by the optional
FlashDrop device. FlashDrop allows easy customisation of the parameter list,
for example, selected parameters can be hidden. For more information, see
MFDT-01 FlashDrop user's manual (3AFE68591074 [English]).
FlashDrop parameter values are activated by setting parameter
APPLIC MACRO to 31 (LOAD FD SET).
Complete long and short parameter lists
FlashDrop parameter list. Does not include short parameter list. Parameters
which are hidden by the FlashDrop device are not visible.
OVERCURRENT
(code: A2001),
UNDERVOLTAGE
(code: A2003) and
Def
0 = NOT SEL
0 = DONE
0 = NO
0 = DEFAULT
9902
Actual signals and parameters
97