User macros

In addition to the standard application macros, it is possible to create three user
macros. The user macro allows the user to save the parameter settings, including
group
time. The panel reference is also saved if the macro is saved and loaded in local
control. The remote control setting is saved into the user macro, but the local control
setting is not.
The steps below show how to create and recall User macro 1. The procedure for the
other two user macros is identical, only the parameter
are different.
To create User macro 1:
• Adjust the parameters.
• Save the parameter settings to the permanent memory by changing parameter
9902
• Press
To recall User macro 1:
• Change parameter
• Press
Note: User macro load restores the parameter settings including group
UP DATA.
Hint: The user can for example switch the drive between three motors without
having to adjust the motor parameters every time the motor is changed. The user
needs only to adjust the settings once for each motor and then to save the data as
three user macros. When the motor is changed, only the corresponding user macro
needs to be loaded, and the drive is ready to operate.
99 START-UP
DATA, into the permanent memory and recall the data at a later
APPLIC MACRO to -1 (USER S1 SAVE).
MENU
ENTER
to save.
9902
MENU
ENTER
to load.
Check that the settings correspond to the motor used.
APPLIC MACRO to 0 (USER S1 LOAD).
9902
APPLIC MACRO values
99 START-
Application macros
77