To change the direction of the motor rotation:
• Disconnect input power from the drive, and wait 5 minutes
for the intermediate circuit capacitors to discharge. Measure
the voltage between each input terminal (U1, V1 and W1)
and earth with a multimeter to ensure that the drive is
discharged.
• Exchange the position of two motor cable phase conductors
at the drive output terminals or at the motor connection box.
• Verify your work by applying input power and repeating the
check as described above.
Set the acceleration time 1 (parameter
TIME 1).
Note: Set also acceleration time 2 (parameter 2205) if two
acceleration times will be used in the application.
Set the deceleration time 1 (parameter
TIME 1).
Note: Set also deceleration time 2 (parameter 2206) if two
deceleration times will be used in the application.
The start-up is now completed. Check that there are no faults
or alarms shown on the display.
Start-up and control with I/O
ACCELERATION/DECELERATION TIMES
2202
2203
FINAL CHECK
The drive is now ready for use.