Hand/Auto Macro; Default I/O Connections; Select - ABB ACS150 User Manual

0.37...4 kw, 0.5...5 hp
Table of Contents

Advertisement

Hand/Auto macro

This macro can be used when switching between two external control devices is
needed. To enable the macro, set the value of parameter
For the parameter default values, see section
macros
see section
Note: Parameter

Default I/O connections

1...10 kohm
Alternative connection
for AI1. If used, switch
IU selector to U
(2...10 V voltage
signal).
1)
In Hand mode, the frequency reference comes
from the integrated potentiometer.
2)
360 degree grounding under a clamp.
on page 65. If you use other than the default connections presented below,
I/O terminals
on page 34.
2108
START INHIBIT must remain in the default setting 0 (OFF).
I/O connection
SCR
AI
GND
2)
+10V
+24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
Relay connection
COM
NC
NO
Default parameter values with different
3)
Signal cable shield (screen)
Frequency reference (Auto): 4...20 mA
Analog input circuit common
Reference voltage: +10 VDC, max. 10 mA
Auxiliary voltage output: +24 VDC, max. 200 mA
Auxiliary voltage output common
Digital input common
Stop (0) / Start (1) (Hand)
Forward (0) / Reverse (1) (Hand)
Hand (0) / Auto (1) control selection
Forward (0) / Reverse (1) (Auto)
Stop (0) / Start (1) (Auto)
4)
Relay output
No fault [Fault (-1)]
3)
Tightening torque = 0.22 N·m / 2 lbf. in
4)
Tightening torque = 0.5 N·m / 4.4 lbf. in.
9902
to 5 (HAND/AUTO).
1)
Application macros
63