32 Supervision - ABB ACS150 series User Manual

0.37...4kw; 0.5...5 hp
Hide thumbs Also See for ACS150 series:
Table of Contents

Advertisement

114
Parameters in the Long parameter mode
Index Name/Selection

32 SUPERVISION

3201
SUPERV 1 PARAM
Actual signals and parameters
Description
Signal supervision. The drive monitors whether certain user selectable
variables are within the user-defined limits. The user may set limits for speed,
current etc. Supervision status can be monitored with relay output. See
parameter group
14 RELAY
Selects the first supervised signal. Supervision limits are defined by
parameters
3202
SUPERV 1 LIM LO and
Example 1: If
3202
SUPERV 1 LIM LO <
Case A =
1401
RELAY OUTPUT 1 value is set to SUPRV 1 OVER. Relay
energizes when value of the signal selected with
exceeds the supervision limit defined by
remains active until the supervised value drops below the low limit defined by
3202
SUPERV 1 LIM LO.
Case B =
1401
RELAY OUTPUT 1 value is set to SUPRV 1 UNDER. Relay
energizes when value of the signal selected with
drops below the supervision limit defined by
relay remains active until the supervised value rises above the high limit
defined by
3203
SUPERV 1 LIM HI.
Value of supervised parameter
HI (par. 3203)
LO (par. 3202)
Case A
Energized (1)
0
Case B
Energized (1)
0
Example 2: If
3202
SUPERV 1 LIM LO >
The lower limit
3203
SUPERV 1 LIM HI remains active until the supervised
signal exceeds the higher limit
limit. The new limit remains active until the supervised signal drops below the
lower limit
3203
SUPERV 1 LIM HI, making it the active limit.
Case A =
1401
RELAY OUTPUT 1 value is set to SUPRV 1 OVER. Relay is
energized whenever the supervised signal exceeds the active limit.
Case B =
1401
RELAY OUTPUT 1 value is set to SUPRV 1 UNDER. Relay is
de-energized whenever the supervised signal drops below the active limit.
Value of supervised parameter
LO (par. 3202)
HI (par. 3203)
Case A
Energized (1)
0
Case B
Energized (1)
0
OUTPUTS.
3203
SUPERV 1 LIM HI.
3203
SUPERV 1 LIM HI
3201
3203
SUPERV 1 LIM HI. The relay
3201
3202
SUPERV 1 LIM LO. The
3203
SUPERV 1 LIM HI
3202
SUPERV 1 LIM LO, making it the active
Active limit
Def
103
SUPERV 1 PARAM
SUPERV 1 PARAM
t
t
t
t
t
t

Advertisement

Table of Contents
loading

Table of Contents