ABB ACS150 series User Manual page 111

0.37...4kw; 0.5...5 hp
Hide thumbs Also See for ACS150 series:
Table of Contents

Advertisement

110
Parameters in the Long parameter mode
Index Name/Selection
3010
STALL FUNCTION
0 = NOT SEL
1 = FAULT
2 = ALARM
3011
STALL FREQUENCY
0.5...50.0 Hz
3012
STALL TIME
10...400 s
3013
UNDERLOAD FUNC
0 = NOT SEL
1 = FAULT
2 = ALARM
3014
UNDERLOAD TIME
10...400 s
Actual signals and parameters
Description
Selects how the drive reacts to a motor stall condition. The protection wakes
up if the drive has operated in a stall region (see the figure below) longer than
the time set by parameter
Current (A)
0.95 · par 2003 MAX CURRENT
Protection is inactive.
The drive trips on fault
MOTOR STALL
to stop.
The drive generates alarm
Defines the frequency limit for the stall function. See parameter
FUNCTION.
Frequency
Defines the time for the stall function. See parameter
FUNCTION.
Time
Selects how the drive reacts to underload. The protection wakes up if
- the motor torque falls below the curve selected by parameter
UNDERLOAD CURVE,
- output frequency is higher than 10% of the nominal motor frequency and
- the above conditions have been valid longer than the time set by parameter
3014
UNDERLOAD TIME.
Protection is inactive.
The drive trips on fault
UNDERLOAD
stop.
The drive generates alarm
Defines the time limit for the underload function. See parameter
UNDERLOAD FUNC.
Time limit
3012
STALL TIME.
Stall region
(code: F0012) and the motor coasts
MOTOR STALL
(code: A2012).
(code: F0017) and the motor coasts to
UNDERLOAD
(code: A2011).
Def
0 = NOT SEL
f
Par. 3011
3010
STALL
20.0 Hz
3010
STALL
20 s
0 = NOT SEL
3015
3013
20 s