Control connection data

Analog input X1A: AI(1)
Auxiliary voltage X1A: +24V
Digital inputs X1A: DI1...DI5
(frequency input DI5)
Frequency input X1A: DI5
Relay output X1A:
COM, NC, NO
Wire size
Torque

Brake resistor connection

Short-circuit protection
(IEC 61800-5-1, IEC 60439-1,
UL 508C)

Efficiency

Degrees of protection

Technical data
Voltage signal, unipolar
Current signal, unipolar
Potentiometer reference value
(X1A: +10V)
Resolution
Accuracy
Voltage
Max. voltage for digital inputs 30 V DC
Type
Input impedance
DI5 can be used either as a digital or as a frequency input.
Frequency input
Type
Max. switching voltage
Max. switching current
Max. continuous current
Relay connections
I/O connections
Relay connections
I/O connections
The brake resistor output is conditionally short-circuit proof by IEC/EN 61800-5-1 and UL
508C. For correct fuse selection, contact your local ABB representative. Rated conditional
short-circuit current as defined in IEC 60439-1 and the short-circuit test current by UL
508C is 100 kA.
Approximately 95 to 98% at nominal power level, depending on the drive size and options
IP20 (cabinet installation) / UL open: Standard enclosure. The drive must be installed in a
cabinet to fulfil the requirements for shielding from contact.
IP20 / NEMA 1: Achieved with an option kit (MUL1-R1) including a hood and a connection
box.
0 (2)...10 V, R
> 312 kohm
in
0 (4)...20 mA, R
= 100 ohm
in
10 V ± 1%, max. 10 mA, R < 10 kohm
0.1%
±1%
24 V DC ± 10%, max. 200 mA
12...24 V DC with internal or external supply
PNP and NPN
2.4 kohm
Pulse train 0...16 kHz (DI5 only)
NO + NC
250 V AC / 30 V DC
0.5 A / 30 V DC; 5 A / 230 V AC
2 A rms
2
1.5...0.20 mm
/16...24 AWG
2
1... 0.14mm
/16...26 AWG
0.5 N·m / 4.4 lbf·in
0.22 N·m / 2 lbf·in