IFP-2000 Installation Manual
4.7

5815XL Installation

The 5815XL SLC expander lets you add additional addressable devices. The maximum
number of SLC devices per panel is 636. The number of 5815XL's is limited by the maximum
number of SBUS devices.)
To install the 5815XL:
1. Make sure power is off at the panel.
2. Mount the 5815XL in the IFP-2000, the RPS-1000 cabinet, or the 5815RMK remote
mounting kit. Use the standoffs located under the control panel board assembly and secure
with screws provided with the 5815XL. See also Model RPS-1000 Installation Instruc-
tions (P/N 151153) or 5815RMK Remote Mounting Kit Installation Instructions (P/N
151391).
3. Connect the 5815XL to the control panel. (See Section 4.7.1.)
4. Use on-board DIPswitches to select an ID#. (See Section 4.5.1.)
5. The new 5815XL module must be added to the system through programming. JumpStart
will add the module automatically (see Section 8.1). You can also add it manually (see
Section 9.2.2). Select a name, if desired (see Section 9.2.1.1).
6. You are now ready to connect SLC devices to the 5815XL (see Section 7.3).
Figure 4-18 is a drawing of the 5815XL board, showing the location of terminals and DIP
switches.
To panel via SBUS
4-18
DIP switches for
setting IDs
Model 5815XL
Figure 4-18 5815XL Board
firealarmresources.com
To SLC loop
151430