IFP-2000 Installation Manual
10. Select Y (monitor line) or N (don't monitor line) by pressing the
press
.

9.6.2.6 Answering Machine Bypass

This option is used in conjunction with the SKSS-2. This feature ensures that an answering
machine will not interfere with communication between the panel and the computer. If an
answering machine is used at the panel site, enable this feature; if an answering machine is not
used, disable the feature.
This option is factory-programmed as Yes (enabled).
The selection made here must match the programming for this option in the Communication
Configuration dialog box of the SKSS-2. See the SKSS-2 manual for more information (PN
151...).
11. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled)
by pressing the

9.6.2.7 Phone Line Unused

This option is used so that you can set unused phones lines to "Yes", then no autotest will be
sent through that line.
This option is factory programmed as No.
12. Select Y or N by pressing the
9.6.3

Daytime/Nighttime Sensitivity

If you need to change the time that sensitivity levels take effect (that is, the time that "Day"
and "Night" begin), follow these steps.
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
7
Display reads:
3. Select
for System Options.
5
4. From the System Options Menu, select
9-26
or
arrow, then press
or
arrow, then press
Initializing
Please wait . . .
2
for Daytime/Nighttime Sensitivity.
firealarmresources.com
or
.
.
arrow, then
151430