IFP-2000 Installation Manual
Operation
Occurs When
Mode
Supervisory
The system
detects a
supervisory
condition.
Trouble
A system trouble
condition
occurs.
Prealarm
A single detector
trips in a 2-
Count zone. (2-
Count means
two detectors
must trip before
an alarm is
reported.)
10-12
System Behavior
The dialer seizes control of the phone line
and calls the central station.
The on-board annunciator sounds a loud,
pulsing beep in the sequence one second
on, one second off.
SUPERVISORY LED is on.
The LCD displays a screen similar to this
one.
The dialer seizes control of the phone line
and calls the central station.
The on-board annunciator sounds a loud,
pulsing beep in the sequence one second
on, nine seconds off.
SYSTEM TROUBLE LED is on.
The LCD displays a screen similar to this
one.
Touchpad PZT beeps.
The LCD displays a screen similar to this
one.
firealarmresources.com
In This Mode You Can
Press
(down arrow) to view the supervisory
condition. A screen similar to this one displays.
Press
to silence the annunciator.
Once the supervisory condition has been corrected,
the system will restore itself automatically.
Press
(down arrow) to view the trouble. A
screen similar to this one displays.
Press
to silence the annunciator.
Once the trouble condition has been fixed, the
system will restore itself automatically.
Press
(down arrow) to view the prealarm. A
screen similar to this one displays.
All system operations are available in this mode.
151430