Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual page 70

Analog/addressable fire system
Table of Contents

Advertisement

IFP-2000 Installation Manual
2. Configure the circuit through programming (see Section 9.5))
Figure 4-32 Class B Notification Appliance Circuit Wiring
Maximum voltage drop per Class B notification circuit is 3V. See Table 4-3
4-32
Alarm Polarity
Shown.
Notification Wiring
Power Limited
Supervised
UL Listed EOL
Model 7628
4.7 kΩ
3A per Circuit, 9A max Combined
Table 4-3 Maximum Impedance Class B
Current
1.0A
1.5A
2.0A
2.5A
3.0A
firealarmresources.com
Regulated 24 VDC
Maximum Impedance
1.5Ω
1.2Ω
1.0Ω
151430