Edit Voice Commands; Jumpstart Autoprogramming - Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual

Analog/addressable fire system
Table of Contents

Advertisement

IFP-2000 Installation Manual
9.6.9

Edit Voice Commands

When a voice output group is selected to be activated by a zone, the cadence pattern specified
in mapping does not apply. For voice output groups, one of six system wide voice commands
will activate depending on the type of event that caused the activation. This menu option
allows you program, the message to be used, the tone used, repeats, and message delays, for
each of the six commands. See also Section 9.3.1 for more information.
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
7
Display reads:
3. Select
for System Options.
5
4. Select
for Edit Voice Commands.
8
5. Select the command you wish to edit (Fire Cmd, Aux 1 Cmd, Aux 2 Cmd, Pre Alarm
Cmd, Trouble Cmd).
6. Select the desired message used for that command.
7. Select the tone to be played between messages. (High-Lo, ANSI Whoop, Cont. Whoop,
ANSI, March Code, California, Steady, or Alert Tone.)
8. Select how many times you wish the message to repeat. (None, 1 - 14, or Continuous.)
9. Select the initial delay time (0 to 28 seconds, in 4 second increments).
10. Select the inter message delay time (4 to 32 seconds, in 4 second increments).
11. Enable/Disable AMR (Allow Message to Repeat after Mic). Y (Yes) or, N (No.
9.7

JumpStart Autoprogramming

JumpStart Auto Programming is used to auto learn the system hardware after devices
have been added or removed from the system. Hardware devices which remain the
same between repeat JumpStarts will retain any customized text or options associated
with the device.
It is best to carefully consider the network ID setting for each panel before the first
jumpstart is performed. Once this is done the panel must be defaulted back to factory
defaults if the network ID settings need to change.
9-36
Initializing
Please wait . . .
IMPORTANT!
firealarmresources.com
151430