5824 Serial/Parallel Interface Module Installation - Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual

Analog/addressable fire system
Table of Contents

Advertisement

IFP-2000 Installation Manual
4.8
5824 Serial/Parallel Interface Module
Installation
The 5824 serial/parallel interface module allows you to connect a printer to the panel, so you
can print a real-time log of system events. Instructions for installing the 5824 appear below.
The 5824 is for ancillary use only.
5824 installation involves the following steps:
1. Make sure power is off at the panel.
2. Connect the 5824 to the panel as shown in Figure 4-20.
Note: Two 5824s per panel maximum.
3. Use the DIP switches on the 5824 board to assign an ID# to the 5824 (see Section 4.5.1).
4. Configure the 5824 device through programming. See Section 4.8.1.
5. Connect a printer to the 5824 as shown in Figure 4-21.
Supervised
Power Limited
4-20
Model 5824 Board
Figure 4-20 5824 Connection to the Panel
firealarmresources.com
Parallel
Cable
Connectors
for Connection
to Printer
Serial
151430