IFP-2000 Installation Manual
Define Output Group Type
Each output group is defined as either a voice output group or a non-voice output group.
Output points that are audio circuits (all circuits on the VIP-50 and VIP-CE4) can only be
assigned to voice output groups. Output points that are non-voice circuits (all other points and
circuits that are on all modules except the VIP-50 and VIP-CE4) are assigned to non-voice
output groups.
Each of the output groups defined as voice can be mapped to a particular Switch and LED on
the VIP-VCM and VIP-SW16. Figure 9-6 illustrates how the numbers selected correspond to
the VIP-VCM and -SW16.
Corresponding
Switch and LED Numbers
Figure 9-6 Corresponding Switch and LED for Mapping Output Groups
7. To get to this menu item repeat steps 1 through 5 of Section 9.4.1.
8. To edit group properties, press
9. Press the
or
10. Press
.
11. Press the
or
make this a non-voice output group.
9.4.2

Add Group

To add a group:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
7
Display reads:
9-12
VIP-VCM
.
2
arrows to select the desired VIP switch number, or enter the number.
arrows to select Y (yes) to make this a voice output group or N (no) to
Initializing