4.13.2.2 Class A Inputs

You can connect conventional Class A switches, such as waterflow switches and pull stations,
directly to the Flexput circuits of the control panel.
To install a Class A switch:
1. Wire the Class A switch as shown in Figure 4-35.
2. Configure the circuit through programming (see Section 9.5).
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-35 uses both Flexput circuit 1 and 2, so in programming it
would be referred to as point 1.
151430
Supervised
Power Limited
Note:
Flexput circuit 1 and 2
used as an example.
Any Flexput point pairing
could be used.
Maximum Impedance per
Circuit is 50Ω
Figure 4-35 Class A initiating Switches
firealarmresources.com
Control Panel Installation
4-35