Configuring For Snmp; Alarm Contact Closures - Cisco ONS 15501 User Manual

Table of Contents

Advertisement

Alarm Contact Closures

Configuring for SNMP

To configure the Cisco ONS 15501 for SNMP, follow these steps:
Connect the Cisco ONS 15501 to an Ethernet LAN using a standard RJ-45 cable.
Step 1
Enter add-snmp-mgr manager-ip to set the SNMP manager IP addresses. The maximum number of
Step 2
SNMP manager IP addresses is 16.
Enter get-snmp-mgr to display the list of SNMP managers.
Step 3
Step 4
Enter del-snmp-mgr manager-ip to delete an SNMP manager entry.
Alarm Contact Closures
The Cisco ONS 15501 provides a front panel, single form C, discrete external alarm output. (See the
"Cisco ONS 15501 Front Panel" section on page 1-7
output is through the eight wires of an RJ-45 connector.
The following events are reported by the discrete external alarms through individual alarm contacts:
The default state of the alarm contacts is Normally Open. Depending on which fault condition occurs,
Note
specific alarm contacts close and cause the corresponding Cisco ONS 15501 LEDs to turn on. (See
the
Table 3-2
Table 3-2
Pinout
1
2
3
4
5
6
7
8
Cisco ONS 15501 User Guide
3-4
Alarm 1—Loss of input power supply or power supply out of range
Alarm 2—Failure in the pump laser bias or pump laser temperature (overheating)
Alarm 3—Loss of input signal or input signal power below threshold
"Cisco ONS 15501 LED Alarm Definitions" section on page 1-8
lists the RJ-45 pinouts for the alarms.
Alarm Pinouts
Alarm
Alarm 1+ (power)
Alarm 1-
Alarm 2+ (major)
Alarm 2-
Alarm 3+ (minor)
Alarm 3-
Alarm 4+ (no connection)
Alarm 4-
Chapter 3
Configuring the Cisco ONS 15501
for additional information.) The external alarm
for additional information.)
78-14134-01, Release 1.0