Inputs 9 and 10 are connected across RTP A and RTP B.
TIP: Recommended external current loop fuses.
Additionally, on RTP A connect the following terminals: 3-22, 4-23, 7-24,
8-25, 15-26, 16-27, 19-29, 20-30
On RTP B connect the following terminals: 1-22, 2-23, 5-24, 6-25, 13-
26, 14-27, 17-28, 18-29

Using an RTP to field wiring the 16 Point AC DI

ATTENTION:
RTP and cables are intended for permanent installation within their own
l
enclosure.
The RTP combines the two groups of 8 inputs into one group of 16.
l
To wire the 16 Point AC DI using an RTP:
Figure A-11: Current connections with 2-wire transmitter
Appendix A - Installing RTP
199