Wiring Guidelines For Ac Input - Honeywell MIWI350 Installation And Operation Manual

Hide thumbs Also See for MIWI350:
Table of Contents

Advertisement

1 About MIWI350
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and;
2. This device must accept any interference received, including interference that may cause undesired
operation.
Note:
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment generates—and can radiate—
radio frequency energy and, if not installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no guarantee that interference will
not occur in a particular installation.
Warning:
Changes or modifications to this unit not expressly approved by the party responsible for
compliance could void the user's authority to operate the equipment.
Caution:
This equipment has been tested. It complies with Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential installation.
This device generates, uses and radiates radio frequency energy. If this device is not installed and used
in accordance with the instructions, it can cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in installation.
Note:
The radiated output power of the device is far below the exposure limits. Nevertheless, use the
device in such a manner that the potential for human contact during normal operation is minimal.

1.4.4 Wiring Guidelines for AC Input

Over current protection
It is required to install an input fuse in-order to protect the equipment from Over current and short circuit.
Recommended Fuse is as below:
INPUT
230VAC
120VAC
12VDC
230/120AC Input Cable Specification
It is required to use a UL/CSA approved cable with working voltage spec of min 300V. Cable shall be
protected with an outer sheath.
Warning:
For AC Input variant, readily accessible two-poled disconnect device must be incorporated in
the fixed wiring.
FUSE RATING
1A
1.5A
2A
VOLTAGE RATING
250VAC Slow blow fuse
250VAC Slow blow fuse
250VAC Slow blow fuse