Jumper Comb; Replaceable Fuses; Ac Output Module Wiring Diagram; Ac Output Module Jumper - Honeywell ControlEdge 900 platform Hardware Planning And Installation Manual

Controledge plc, controledge rtu
Hide thumbs Also See for ControlEdge 900 platform:
Table of Contents

Advertisement

130
required) to connect the high-current loads to every other
output - for example, outputs 1, 3, 5, 7 or 2, 4, 6, 8. This
distributes heat more evenly across the heat sink.

Jumper Comb

A ten-position jumper comb is available for inter-connecting all L1
(Hot) terminals (1, 3, 5, 7, 9, 11, 13, 15, 17, 19). See
Jumper
section.

Replaceable Fuses

Each output circuit on the AC Output Module includes a (plug-in)
replaceable fuse.
Replacement fuse is from Wickmann, part #3741315041. This is a
3.15 Amp time lag fuse with UL/CSA approval for 250 V AC.
Figure 5-39: AC Output Module Wiring Diagram
Figure 5-40: AC Output Module Jumper
AC Output Module