Using an RTP to field wire the UIO

ATTENTION:
The maximum current load on RTP cable series 900RTC-L12xx is 2.8A
l
and 900RTC-H12xx is 4.2A per module for UIO.
RTP and cables are intended for permanent installation within their own
l
enclosure.
The RTP combines the two groups of 8 (RTP side) inputs into one group
l
of 16 (UIO side).
For digital output, up to 4 A is limited at module level and for each
l
channel 500 mA.
To wire the UIO using an RTP:
1. Mount the RTP cable assembly to ControlEdge 900 Controller. See the
following figure for the example installation diagram.
a. Remove the relevant key tabs from the terminal block to allow connection
with the module.
Appendix A - Installing RTP
189