The field wire must be connected with one of the following OUT pins
(together with the branch). One of the OUT pins can be used for
connecting the return field wire.
n
n

Universal Analog Input Module (UAI) Wiring

The Universal Analog Input Module has eight inputs, which can
include any combination of the following input types: RTD, TC, Ohms,
Millivolt, Volt, or Milliamp. Figure shows wiring examples of each of
the analog input types. An example of wiring for eight TC inputs is
given in
Specifications for this module, see
(UAI)
Table 5-20: Typical Thermocouple resistance in Ohms per Double Foot @ 68 degrees F
AWG
Diameter
Type
No.
inches
K
10
0.102
0.058 0.034 0.029
12
0.081
0.091 0.054 0.046
14
0.064
0.146 0.087 0.074
16
0.051
0.230 0.137 0.117
18
0.040
0.374 0.222 0.190
20
0.032
0.586 0.357 0.298
24
0.0201
1.490 0.878 0.7526 1.78
26
0.0159
2.381 1.405 1.204
Two DO channels with a two pin branch
Three DO channels with a three pin branch
Analog Input Wiring - Eight TCs
section.
ATTENTION:
To indicate sensor failure the Analog Input software will output
a warning if thermocouple resistance > 80 ohms. Use
appropriate gauge wiring to prevent inaccurate failure
warnings.
Type
Type T
J
section.
Universal Analog Input Module
Type S
Type R
Type
Pt/
Pt/
E
PT110
PT113
0.069 0.018
0.018
0.109 0.028
0.029
0.175 0.045
0.047
0.276 0.071
0.073
0.448 0.116
0.119
0.707 0.185
0.190
0.464
0.478
2.836 0.740
0.760
Type
Type
W5/
W/
W26
W26
0.023
0.020
0.037
0.031
0.058
0.049
0.092
0.078
0.148
0.126
0.235
0.200
0.594
0.560
0.945
0.803