Minimum Pulse Width: 2.25 μsec
n
Quadrature Counter: 32 bits signed
n
Quadrature Modes: For variable resolution there are three count
n
modes for the Pulse/Quadrature input: X1: rising edges of signal A
are counted (increment); falling edges of signal A (decrement) X2:
rising and falling edges of signal A are counted X4: rising and
falling edges of signals A and B are counted
Quadrature LEDs: Two LEDs indicate UP and DOWN direction of
n
counting.

Analog Output Module (4 Channels)

4 channel 0-21.8 mA, range selectable analog output
n
Load resistance: 750 ohms maximum
n
Accuracy: 0.1% full scale
n
D/A resolution: 12 Bitsat reference conditions
n
Modules per rack: 10 max, up to 12 with product ambient
n
temperature de-rating. See the figure below:
Update rate: 500 ms
n
Minimum current sensing: >3.5 mA per output
n
Isolation:
n
500V DC channel to channel
l
600V DC isolation from logic
l
Output Verification: Readback to controller that indicates output
n
current flowing.
D/A resolution: 12 bits
n
Figure 5-16: De-rating of AO modules