Digital Output Module (8 Channels) - Ac Voltage Type; Digital Output Module (32 Channels) - Dc Voltage Type - Honeywell ControlEdge 900 platform Hardware Planning And Installation Manual

Controledge plc, controledge rtu
Hide thumbs Also See for ControlEdge 900 platform:
Table of Contents

Advertisement

Update Rate: 6 ms Maximum
n
Switching current: 2.6mA norminal
n
Galvanic Isolation: Between Field wiring (input or output) and
n
Module
Power supply Loading:
n
5 V; 130 mA maximum
l
24v; 40 mA maximum
l
Digital Output Module (8 Channels) - AC Voltage
Type
DO AC Voltage type module supports:
Channel Density: 8 Channels
l
Output Type: Triac (Zero switching voltage)
l
Input voltage range: 85 V AC to 240 V AC.
l
Isolation: Galvanic ally isolated per Channel to channel and
l
channel to rack.
Transient Overload Voltage Protection
l
Maximum Load Current: 2 A per channel and 8 A max. per module
l
(Resistive load)
OFF to ON Response Time*: 3 ms + 0.5 line cycle max
l
ON to OFF Response Time*: 3 ms + 0.5 line cycle max
l
Power Supply Loading: 5 V: 220 mA max and 24V: 0 mA
l
Per channel Field-replaceable fuse support
l
20 pin EURO style terminal block
l
RTP support. For more information, see Using an RTP to field
l
wiring the 8 Point AC DO section.
TIP:
*Excluding controllers scan time and excluding transmission
time from module to rack.
Digital Output Module (32 Channels) - DC Voltage
Type
The Digital Output Module – DC Voltage Type is current sourcing type
module.
DO DC Voltage type module supports:
99