6. Load C300 Controller Configuration

6.2. Initial load order guidelines

6.2
Initial load order guidelines
Make the initial load of control strategy components from the Project tab in the following
order to minimize possible load interaction generated error messages. Use the Load rather
than the Load with Contents command.
Order
1
A - C300 Platform
B - C300 IOLINK1
C - C300 IOLINK2
D - CEEC300
2
CM or SCM*
* Refer to the Control Building User's Guide for more information about loading these
components.
Notes:
Loading the C300 platform block from project without contents will load the associated
CEE and IOLink blocks. All blocks must be configured before loading.
Appropriate errors will be returned in case of load failures.
For example, C300 not physically present at the configured address, C300 IOLINK
Block state FAILED, C300 CEE Block state FAILED, IOM physically not present,
configuration mismatches, and so on).

Component deletion considerations

Control Strategy edits must be performed from the Project tab only.
Deleting blocks from the Project tab eliminates them from the Project version of the
database only. Only blocks that are not loaded can be deleted. Delete loaded blocks
from the Monitoring tab first before deleting them from the Project tab.
Deleting blocks from the Monitoring tab eliminates them from the controller, Server
and loaded version of the database. The blocks remain in the Project version of the
database.