7. C300 Controller Operation

7.9. Initiating Become Primary command

7.9
Initiating Become Primary command
Perform the following procedure to manually cause an unsynchronized secondary
controller to transition into a primary role in the absence of a partner controller.

Prerequisites

You can view active redundant C300 Controller pair on the Monitoring tab in
Control Builder.
The unsynchronized secondary controller has no view to a partner controller across
the redundancy cable and the primary IP address is currently not occupied.

Commanding Become Primary

To issue become primary command, perform the following steps.
Step
1
In the Monitoring tab, double-click the secondary C300 icon. The
Parameters configuration form appears.
2
Click the Redundancy tab.
3
Click Become Primary.
4
Click Yes to confirm the action and issue the Become Primary command.
5
Confirm that the Secondary C300 Controller assumes the Primary role.
6
Click OK to close the Parameters form.
7
This completes the procedure.
196
Series 8 C300 Controller User's Guide