Initiating Synchronization Command; Prerequisites; Commanding Synchronization - Honeywell C300 User Manual

Series 8
Hide thumbs Also See for C300:
Table of Contents

Advertisement

7. C300 Controller Operation

7.7. Initiating Synchronization command

7.7
Initiating Synchronization command
To initiate a synchronization command manually to a redundant C300 Controller pair,
perform the following steps.

Prerequisites

You can view active redundant C300 Controller pair on the Monitoring tab in Control
Builder.

Commanding synchronization

Step
1
In the Monitoring tab, double-click the primary C300 icon to The Parameters
configuration form appears.
2
Click the Redundancy tab.
3
Click Enable Synchronization.
4
Click Yes to confirm the action and issue the synchronize command.
5
Confirm that the Auto Synchronization State becomes ENABLED and
confirm that sync cycles in the primary C300 Controller's 4-character display.
6
Click OK to close the Parameters form.
7
This completes the procedure.
194
Series 8 C300 Controller User's Guide
Honeywell
Action
R500
April 2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents