Advertisement

Section 3
Basic functions
3.10.1
3.10.1.1
80
Power output contacts are used when the current rating requirements of the
contacts are high, for example, for controlling a breaker, such as energizing the
breaker trip and closing coils.
The contacts used for external signalling, recording and indicating, the signal
outputs, need to adjust to smaller currents, but they can require a minimum current
(burden) to ensure a guaranteed operation.
The IED provides both power output and signal output contacts. To guarantee
proper operation, the type of the contacts used are chosen based on the operating
and reset time, continuous current rating, make and carry for short time, breaking
rate and minimum connected burden. A combination of series or parallel contacts
can also be used for special applications. When appropriate, a signal output can
also be used to energize an external trip relay, which in turn can be confiugred to
energize the breaker trip or close coils.
Using an external trip relay can require an external trip circuit
supervision relay. It can also require wiring a separate trip relay
contact back to the IED for breaker failure protection function.
All contacts are freely programmable, except the internal fault output IRF.

Power output contacts

Power output contacts are normally used for energizing the breaker closing coil and
trip coil, external high burden lockout or trip relays.

Dual single-pole power outputs PO1 and PO2

Dual (series-connected) single-pole (normally open/form A) power output contacts
PO1 and PO2 are rated for continuous current of 8 A. The contacts are normally
used for closing circuit breakers and energizing high burden trip relays. They can
be arranged to trip the circuit breakers when the trip circuit supervision is not
available or when external trip circuit supervision relay is provided.
The power outputs are included in slot X100 of the power supply module.
1YHT530004D05 D