Section 3
Basic functions
3.11.3
3.11.4
Table 56:
RTD input settings
Parameter
Input mode
Input maximum
Input minimum
Value unit
Value maximum
Value minimum
Val high high limit
Table continues on next page
94

Signals

Table 55:
X130 (RTD/mA) analog input signals
Name
ALARM
WARNING
AI_VAL1
AI_VAL2
AI_VAL3
AI_VAL4
AI_VAL5
AI_VAL6
AI_VAL7
AI_VAL8

Settings

Values (Range)
Unit
1=Not in use
2=Resistance
10=Pt100
11=Pt250
20=Ni100
21=Ni120
22=Ni250
30=Cu10
0...2000
0...2000
1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
-10000.0...10000.0
-10000.0...10000.0
-10000.0...10000.0
Type
Description
BOOLEAN
General alarm
BOOLEAN
General warning
FLOAT32
mA input, Connectors 1-2, instantaneous value
FLOAT32
mA input, Connectors 3-4, instantaneous value
FLOAT32
RTD input, Connectors 5-6-11c, instantaneous
value
FLOAT32
RTD input, Connectors 7-8-11c, instantaneous
value
FLOAT32
RTD input, Connectors 9-10-11c, instantaneous
value
FLOAT32
RTD input, Connectors 13-14-12c, instantaneous
value
FLOAT32
RTD input, Connectors 15-16-12c, instantaneous
value
FLOAT32
RTD input, Connectors 17-18-12c, instantaneous
value
Step
Default
1=Not in use
1
2000
1
0
1=Dimensionless
10000.0
-10000.0
10000.0
1YHT530004D05 D
Description
Analogue input mode
Maximum analogue input value for mA
or resistance scaling
Minimum analogue input value for mA or
resistance scaling
Selected unit for output value format
Maximum output value for scaling and
supervision
Minimum output value for scaling and
supervision
Output value high alarm limit for
supervision
Technical Manual
615 series

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents