Section 9
Control functions
9.5.16
758

Signals

Table 636:
OLATCC Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
U_AB
SIGNAL
TR1_TAP_POS
INT32
TR2_TAP_POS
INT32
TR3_TAP_POS
INT32
RAISE_LOCAL
BOOLEAN
LOWER_LOCAL
BOOLEAN
TAPCHG_FLLW
BOOLEAN
PARALLEL
BOOLEAN
AUTO
BOOLEAN
CON_STATUS
BOOLEAN
LTC_BLOCK
BOOLEAN
TCO
BOOLEAN
RSV
BOOLEAN
TR1_I_AMPL
FLOAT32
TR1_I_ANGL
FLOAT32
TR2_I_AMPL
FLOAT32
TR2_I_ANGL
FLOAT32
TR3_I_AMPL
FLOAT32
TR3_I_ANGL
FLOAT32
Table 637:
OLATCC Output signals
Name
Type
RAISE_OWN
BOOLEAN
LOWER_OWN
BOOLEAN
FLLW1_CTL
INT32
FLLW2_CTL
INT32
FLLW3_CTL
INT32
ALARM
BOOLEAN
PAR_FAIL
BOOLEAN
Table continues on next page
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Phase-to-phase voltage AB
0
Integer value representing tap changer position of
transformer 2
0
Integer value representing tap changer position of
transformer 3
0
Integer value representing tap changer position of
transformer 4
0=False
Raise command input from configuration
0=False
Lower command input from configuration
0=False
Change follower tap position (stop, lower, higher)
0=False
Parallel or single operation
0=False
Auto/Manual indication
0=False
Network connection status of the (own) transformer
0=False
External signal for blocking of automatic operation
0=False
Tap changer operating input
0=False
Reduce set voltage active
0.00
Received current magnitude from transformer 1
0.00
Received current angle from transformer 1
0.00
Received current magnitude from transformer 2
0.00
Received current angle from transformer 2
0.00
Received current magnitude from transformer 3
0.00
Received current angle from transformer 3
Description
Raise command for own transformer
Lower command for own transformer
Lower/Raise command for follower transformer 1
in the Master/Follower operation mode
Lower/Raise command for follower transformer 2
in the Master/Follower operation mode
Lower/Raise command for follower transformer 3
in the Master/Follower operation mode
Alarm status
Parallel failure detected