Section 3
Basic functions
3.14.9
3.14.9.1
3.14.9.2
134

Generic control points function block SPCGGIO

Function block

GUID-B1380341-22B1-4C7E-A57B-39DBBB9D7B92 V1 EN
Figure 68:
Function block

Functionality

The generic control points function SPCGGIO contains 16 independent control
points. SPCGGIO offers the capability to activate its outputs through a local or
remote control. The local control request can be issued through the buttons in the
single-line diagram or via inputs and the remote control request through
communication. The rising edge of the input signal is interpreted as a control
request, and the output operation is triggered. When remote control requests are
used the control points behaves as persistent.
The Loc Rem restriction setting is used for enabling or disabling the restriction for
SPCGGIO to follow the R/L button state. If Loc Rem restriction is "True", as it is
by default, the local or remote control operations are accepted according to the R/L
button state.
Each of the 16 generic control point outputs has the Operation mode, Pulse length
and Description setting. If Operation mode is "Toggle", the output state is toggled
for every control request received. If Operation mode is "Pulsed", the output pulse
of a preset duration (the Pulse length setting) is generated for every control request
received. The Description setting can be used for storing information on the actual
use of the control point in application, for instance.
The BLOCK input can be used for blocking the functionality of the outputs. The
operation of the BLOCK input depends on the Operation mode setting. If Operation
mode is "Toggle", the output state freezes and cannot be changed while the BLOCK
input is active. If Operation mode is "Pulsed", the activation of the BLOCK input
resets the outputs to the "False" state and further control requests are ignored while
the BLOCK input is active.