1YHT530004D05 D
3.13.3
3.13.3.1
3.13.3.2
3.13.4
3.13.4.1
3.13.4.2
615 series
Technical Manual

QTY_GOOSE_COMM function block

Functionality

The QTY_GOOSE_COMM function block evaluates the peer IED communication
status from the quality bits of the input signal and passes it as a Boolean signal to
the application.
The IN input can be connected to any GOOSE application logic output signal, for
example, GOOSERCV_BIN.
The OUT output indicates the communication status of the GOOSE function block.
When the output is in the true (1) state, the GOOSE communication is active. The
value false (0) indicates communication timeout.

Signals

Table 79:
QTY_GOOSE_COMM Input signals
Name
Type
IN
Any
Table 80:
QTY_GOOSE_COMM Output signals
Name
OUT

T_HEALTH function block

Function block

GUID-B5FCAE66-8026-4D5F-AC38-028E5A8171BB V1 EN
Figure 40:
Function block
Functionality
The T_HEALTH function evaluates enumerated data of "Health" data attribute.
This function block can only be used with GOOSE.
The IN input can be connected to GOOSERCV_ENUM function block, which is
receiving the LD0.LLN0.Health.stVal data attribute sent by another IED.
Default
0
Type
BOOLEAN
Section 3
Basic functions
Description
Input signal
Description
Output signal
105