Monitored Data - ABB RED615 Technical Manual

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Section 4
Protection functions
4.2.5.8
4.2.5.9
344

Monitored data

Table 328:
HAEFPTOC Monitored data
Name
Type
START_DUR
FLOAT32
I_HARM_RES
FLOAT32
BLKD_I_REF
BOOLEAN
HAEFPTOC
Enum
Technical data
Table 329:
HAEFPTOC Technical data
Characteristic
Operation accuracy
1)2)
Start time
Reset time
Reset ratio
Operate time accuracy in definite time mode
Operate time accuracy in IDMT mode
Suppression of harmonics
1) Fundamental frequency current = 1.0 x In. Harmonics current before fault = 0.0 x In, harmonics fault
current 2.0 x Start value. Results based on statistical distribution of 1000 measurement.
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x In, Start value multiples in range of 2 to 20
Values (Range)
Unit
0.00...100.00
%
0.0...30000.0
A
0=False
1=True
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the current
measured: fn ±2 Hz
±5 % of the set value or ±0.004 x In
Typical 77 ms
< 40 ms
Typical 0.96
±1.0% of the set value or ±20 ms
3)
±5.0% of the set value or ±20 ms
-50dB at f= fn
-3dB at f= 13 x fn
1YHT530004D05 D
Description
Ratio of start time /
operate time
Calculated harmonics
current
Current comparison
status indicator
Status
615 series
Technical Manual