GUID-5E0D15BA-ADA9-4FE0-A85D-5C6E86D7E32B V1 EN
Figure 222:
Alternative connection example of current transformers of Type 2
The CT secondary currents often differ from the rated current at the rated load of
the power transformer. The CT transforming ratios can be corrected on both sides
of the power transformer with the CT ratio Cor Wnd 1 and CT ratio Cor Wnd 2
settings.

Signals

Table 340:
TR2PTDF Input signals
Name
Type
I_A1
SIGNAL
I_B1
SIGNAL
I_C1
SIGNAL
I_A2
SIGNAL
I_B2
SIGNAL
Table continues on next page
Protection functions
X120
1/5A
7
8
N
9
1/5A
10
N
11
1/5A
12
N
X120
1
1/5A
2
N
3
1/5A
4
N
5
1/5A
6
N
Default
Description
0
Phase A primary current
0
Phase B primary current
0
Phase C primary current
0
Phase A secondary current
0
Phase B secondary current
Section 4
IL1
IL2
IL3
IL1B
IL2B
IL3B