Monitored Data - ABB RED615 Technical Manual

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Section 4
Protection functions
4.6.1.8
4.6.1.9
4.6.2
4.6.2.1
502

Monitored data

Table 428:
FRPFRQ Monitored data
Name
Type
START_DUR
FLOAT32
ST_DUR_OFRQ
FLOAT32
ST_DUR_UFRQ
FLOAT32
ST_DUR_FRG
FLOAT32
FRPFRQ
Enum
Technical data
Table 429:
FRPFRQ Technical data
Characteristic
Operation accuracy
Start time
Reset time
Operate time accuracy
Load shedding and restoration LSHDPFRQ
Identification
Function description
Load shedding and restoration
Values (Range)
Unit
0.00...100.00
%
0.00...100.00
%
0.00...100.00
%
0.00...100.00
%
1=on
2=blocked
3=test
4=test/blocked
5=off
f>/f<
df/dt
f>/f<
df/dt
IEC 61850
IEC 60617
identification
identification
LSHDPFRQ
UFLS/R
1YHT530004D05 D
Description
Start duration
Start duration
Start duration
Start duration
Status
Value
±10 mHz
±100 mHz/s (in range |df/dt| < 5
Hz/s)
± 2.0% of the set value (in
range 5 Hz/s < |df/dt| < 15 Hz/s)
< 80 ms
< 120 ms
< 150 ms
±1.0% of the set value or ±30 ms
ANSI/IEEE C37.2
device number
81LSH
615 series
Technical Manual