1YHT530004D05 D
3.14.8.3
615 series
Technical Manual
Table 142:
Truth table for CONTROL
CTRL_OFF
CTRL_LOC
TRUE
any
FALSE
TRUE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
1) If station authority is not in use, the CTRL_STA input is interpreted as CTRL_REM.
The station authority check based on the IEC 61850 command originator category
in control command can be enabled by setting the value of the Station authority
setting to "Station, Remote" (The command originator validation is performed only
if the LR control setting is set to "Binary input"). The station authority check is not
in use by default.

Signals

Table 143:
CONTROL input signals
Name
Type
BOOLEAN
CTRL_OFF
BOOLEAN
CTRL_LOC
BOOLEAN
CTRL_STA
BOOLEAN
CTRL_REM
Table 144:
CONTROL output signals
Name
OFF
LOCAL
STATION
REMOTE
Input
CTRL_REM
1)
CTRL_STA
any
any
any
any
TRUE
any
FALSE
TRUE
FALSE
FALSE
Default
0
0
0
0
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Section 3
Basic functions
Output
OFF = TRUE
LOCAL = TRUE
STATION =
TRUE
REMOTE = TRUE
OFF = TRUE
Description
Control input OFF
Control input Local
Control input Station
Control input Remote
Description
Control output OFF
Control output Local
Control output Station
Control output Remote
131