Section 4
Protection functions
4.3.3.6
4.3.3.7
Table 348:
LREFPNDF Group settings
Parameter
Operate value
Minimum operate time
Restraint mode
Start value 2.H
Table 349:
LREFPNDF Non group settings
Parameter
Operation
Reset delay time
CT connection type
430

Signals

Table 346:
LREFPNDF Input signals
Name
I_A
I_B
I_C
Io
BLOCK
Table 347:
LREFPNDF Output signals
Name
OPERATE
START
BLK2H
Settings
Values (Range)
Unit
5...50
%In
40...300000
ms
1=None
2=Harmonic2
10...50
%In
Values (Range)
Unit
1=on
5=off
0...60000
ms
1=Type 1
2=Type 2
Type
Default
Description
SIGNAL
0
Phase A current
SIGNAL
0
Phase B current
SIGNAL
0
Phase C current
SIGNAL
0
Residual current
BOOLEAN
0=False
Block signal for activating the blocking mode
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
BOOLEAN
2nd harmonic block
Step
Default
1
5
1
40
1=None
1
50
Step
Default
1=on
1
20
2=Type 2
1YHT530004D05 D
Description
Operate value
Minimum operate time
Restraint mode
The ratio of the 2. harmonic to
fundamental component required for
blocking
Description
Operation Off / On
Reset delay time
CT connection type
Technical Manual