Definite Time Characteristics - ABB RED615 Technical Manual

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
Section 11
11.1
11.1.1
615 series
Technical Manual
General function block features

Definite time characteristics

Definite time operation
The DT mode is enabled when the Operating curve type setting is selected either as
"ANSI Def. Time" or "IEC Def. Time". In the DT mode, the OPERATE output of
the function is activated when the time calculation exceeds the set Operate delay
time.
The user can determine the reset in the DT mode with the Reset delay time setting,
which provides the delayed reset property when needed.
The Type of reset curve setting has no effect on the reset method
when the DT mode is selected, but the reset is determined solely
with the Reset delay time setting.
The purpose of the delayed reset is to enable fast clearance of intermittent faults,
for example self-sealing insulation faults, and severe faults which may produce
high asymmetrical fault currents that partially saturate the current transformers. It
is typical for an intermittent fault that the fault current contains so called drop-off
periods, during which the fault current falls below the set start current, including
hysteresis. Without the delayed reset function, the operate timer would reset when
the current drops off. In the same way, an apparent drop-off period of the
secondary current of the saturated current transformer can also reset the operate timer.
General function block features
Section 11
791