Section 4
Protection functions
4.2.4.7
334
The admittance characteristic is set to cover the total admittance of the protected
feeder with a proper margin, see
Conductance forward = 1.73 mS · 0.2 ≈ 0.35 mS
Conductance reverse = -1.0 mS (valid range apprx. 0.5 · 1.15 - 1.2 · 1.73 = -0.6...-2.1)
Susceptance forward = 0.1 mS
Susceptance reverse = -1.15 mS · 1.2 ≈ -1.4 mS
5
Go (mS)
4
3
2
1
0
-1
Backward fault:
-2
Yo ≈ -j*1.15mS
-3
-4
-5
-5
-4
-3
-2
-1
0
1
GUID-AE9BB46E-B927-43F6-881A-A96D3410268D V1 EN
Figure 172:
Admittances of the example

Signals

Table 317:
EFPADM Input signals
Name
Type
Io
SIGNAL
Uo
SIGNAL
BLOCK
BOOLEAN
RELEASE
BOOLEAN
Table 318:
EFPADM Output signals
Name
Type
OPERATE
BOOLEAN
START
BOOLEAN
Figure
172.
5
4
3
2
1
0
Bo (mS)
-1
-2
Forward fault,
Yo ≈ 1.73+j*Bo mS
-3
-4
-5
-5
-4
2
3
4
5
Default
Description
0
Residual current
0
Residual voltage
0=False
Block signal for activating the blocking mode
0=False
External trigger to release neutral admittance
protection
Description
Operate
Start
1YHT530004D05 D
Go (mS)
OPERATE
OPERATE
0.1 mS
-1.4 mS
0.35 mS
-1.0 mS
OPERATE
OPERATE
-3
-2
-1
0
1
2
3
615 series
Technical Manual
Bo (mS)
4
5