Section 8
Measurement functions
8.1.6
8.1.6.1
8.1.6.2
8.1.6.3
8.1.6.4
Table 548:
RESCMMXU Non group settings
Parameter
Operation
Measurement mode
A Hi high limit res
A high limit res
A deadband res
638

Residual current measurement RESCMMXU

Identification
Function description
Residual current measurement
Function block
A070778 V2 EN
Figure 347:
Function block
Signals
Table 546:
RESCMMXU Input signals
Name
Io
BLOCK
Table 547:
RESCMMXU Output signals
Name
HIGH_ALARM
HIGH_WARN
Settings
Values (Range)
Unit
1=on
5=off
1=RMS
2=DFT
0.00...40.00
xIn
0.00...40.00
xIn
100...100000
IEC 61850
identification
RESCMMXU
Type
Default
Description
SIGNAL
0
Residual current
BOOLEAN
0=False
Block signal for all binary outputs
Type
Description
BOOLEAN
High alarm
BOOLEAN
High warning
Step
Default
1=on
2=DFT
0.20
0.05
2500
1YHT530004D05 D
IEC 60617
ANSI/IEEE C37.2
identification
device number
Io
Io
Description
Operation Off / On
Selects used measurement mode
High alarm current limit
High warning current limit
Deadband configuration value for
integral calculation. (percentage of
difference between min and max as
0,001 % s)
Technical Manual