Figure 17:
Dual single-pole power output contacts PO1 and PO2

Double-pole power outputs PO3 and PO4 with trip circuit supervision

The power outputs PO3 and PO4 are double-pole normally open/form A power
outputs with trip circuit supervision.
When the two poles of the contacts are connected in series, they have the same
technical specification as PO1 for breaking duty. The trip circuit supervision
hardware and associated functionality which can supervise the breaker coil both
during closing and opening condition are also provided. Contacts PO3 and PO4 are
almost always used for energizing the breaker trip coils.
X100
6
7
8
9
Section 3
Basic functions
81