Section 5
Protection related functions
5.2.6
5.2.7
Table 466:
CCBRBRF Non group settings
Parameter
Operation
Current value
Current value Res
CB failure trip mode
CB failure mode
CB fail retrip mode
Retrip time
CB failure delay
CB fault delay
Measurement mode
Trip pulse time
Start latching mode
550

Signals

Table 464:
CCBRBRF Input signals
Name
I_A
I_B
I_C
Io
BLOCK
START
POSCLOSE
CB_FAULT
Table 465:
CCBRBRF Output signals
Name
CB_FAULT_AL
TRBU
TRRET
Settings
Values (Range)
Unit
1=on
5=off
0.05...2.00
xIn
0.05...1.00
xIn
1=2 out of 4
2=1 out of 3
3=1 out of 4
1=Current
2=Breaker status
3=Both
1=Off
2=Without Check
3=Current check
0...60000
ms
0...60000
ms
0...60000
ms
2=DFT
3=Peak-to-Peak
0...60000
ms
1=Rising edge
2=Level sensitive
Type
Default
Description
SIGNAL
0
Phase A current
SIGNAL
0
Phase B current
SIGNAL
0
Phase C current
SIGNAL
0
Residual current
BOOLEAN
0=False
Block CBFP operation
BOOLEAN
0=False
CBFP start command
BOOLEAN
0=False
CB in closed position
BOOLEAN
0=False
CB faulty and unable to trip
Type
Description
BOOLEAN
Delayed CB failure alarm
BOOLEAN
Backup trip
BOOLEAN
Retrip
Step
Default
1=on
0.05
0.30
0.05
0.30
1=2 out of 4
1=Current
1=Off
10
20
10
150
10
5000
2=DFT
10
150
1=Rising edge
1YHT530004D05 D
Description
Operation Off / On
Operating phase current
Operating residual current
Backup trip current check mode
Operating mode of function
Operating mode of retrip logic
Delay timer for retrip
Delay timer for backup trip
Circuit breaker faulty delay
Phase current measurement mode of
function
Pulse length of retrip and backup trip
outputs
Start reset delayed or immediately