1YHT530004D05 D
4.1.7.7
Table 247:
JAMPTOC Non group settings
Parameter
Values (Range)
Operation
Start value
Operate delay time
Reset delay time
4.1.7.8
4.1.7.9
615 series
Technical Manual
Table 246:
JAMPTOC Output signals
Name
OPERATE
Settings
Unit
1=on
5=off
0.10...10.00
xIn
100...120000
ms
0...60000
ms
Monitored data
Table 248:
JAMPTOC Monitored data
Name
START
START_DUR
JAMPTOC
Technical data
Table 249:
JAMPTOC Technical data
Characteristic
Operation accuracy
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Type
Description
BOOLEAN
Operate
Step
Default
1=on
0.01
2.50
10
2000
1
100
Type
Values (Range)
BOOLEAN
0=False
1=True
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the current
measured: f
±1.5% of the set value or ±0.002 x I
< 40 ms
Typical 0.96
< 35 ms
±1.0% of the set value or ±20 ms
Section 4
Protection functions
Description
Operation Off / On
Start value
Operate delay time
Reset delay time
Unit
Description
Start
%
Ratio of start time /
operate time
Status
±2 Hz
n
n
243